Calculations of overcurrent and
earthfault relay settings of transformer is monotonous and mechanized job.
Hence now a days use of Excel Sheet for such calculations is very common. Here
two excel sheets has been developed viz.
For understanding the formulae used
for calculations proper range names are adopted throughout the sheet as shown
below for better understanding of the calculation method. Note that calculation
range and setting result range are kept protected to avoid accidental changes.
However no protection password is adopted for the sheet.
Readers are encouraged for
downloading the Excel Sheet. Also they can experiment with the sheet; or even
can change the formulae as per custom needs if required. Such study of the
formulae used in sheet and experimenting with sheet will make it possible to
develop own calculation sheets and also improve overall understanding of the
setting methodology.
Here two practical examples
calculations of overcurrent and earthfault relay settings are done using two
Excel Sheet mentioned above and covered in next section. Calculation steps
shown in example are self-explanatory. Readers are requested to go through the
example carefully and preferably with hand calculations before to start of
using the Excel Sheet.