For transformer operating in parallel we can have different protection schemes as shown below along with respective comments.
This is the most
preferred scheme where we have directional as well as non-directional relays
(or separately assigned contacts of same relay) on LV side. LV side Directional
relay provides selective tripping of transformer along with or in case of
non-operation of Differential (Main) protection. Thus operation of this relay
(output contact) operates HV side as well as LV side breaker of the
transformer. Whereas LV side Non-Directional relay provides simple means for
protection of transformer against un-cleared fault by feeder breaker. Hence
operation of this relay (or output contact) operates only LV side breaker of
the transformer. Transformer HV side protection shall always be simple as a
second defence level hence it is non-directional.
In some cases for LV
side relay it is not possible to configure output contacts separately for
Non-Directional characteristics. Instead we may configure output contacts for
Forward (Towards Transformer) and Reverse (Towards Feeder) direction separately.
Thus In such case we may use protection scheme as shown here.
It is also possible that we may not have
Directional relay on LV side even though may need to operate the transformer in
parallel. In such case Non-directional relay provided on transformer LV side
may serve the basic purpose of providing necessary protection to transformer
against through fault. However in case of fault in transformer differential
zone we can’t expect selective tripping by overcurrent earth fault relay. But
the chances to render this duty by overcurrent earth fault relay are very
remote. Thus we may use the protection scheme as shown here as compromised
protection scheme.
Though the scheme as shown here is
most economical and sufficient it is not recommended because protection of
transformer against through fault has to be rendered by transformer HV side
relay only. This may be risky decision considering cost of the transformer.
Can the reasons for 'Not Recommended' scheme be added for making it more simple and illustrious...
ReplyDeleteHere protection of transformer entirely depend on HV side relay. IF the transformer HV side relay fails to operate; protection duty goes directly to all source S/S. If there are more than one sources (Now a days which is common); chances of timely operation of upper S/S protection again reduces due to distribution of fault current among many sources and transformer may even fail
ReplyDelete