For any ICT tertiary winding
is having lowest voltage hence thus it is called as LV winding and nomenclature
of ICT winding is as- Primary Winding – HV, Secondary Winding – IV and Tertiary
Winding – LV. Though the ICT is represented by three terminal network with
impedances as ZP, ZS, and ZT they are not
directly available on ICT nameplate. Instead whatever given is
Zps
– Leakage impedance measured from primary with secondary short-circuited and
tertiary open
Zpt
– Leakage impedance measured from primary with tertiary short-circuited and
secondary open
Zst
– Leakage impedance measured from secondary with tertiary short-circuited and
primary open
And
using following formulae we can have ZP, ZS, and ZT
Note: ICT are auto
transformers and if neutral is solidly grounded (without intentional insertion
of earthig resistance) its modeling is same as three winding transformer.
Generally ICT neutral is grounded solidly.