While transformer operating
separately LV side protection can be provided by Non-Directional relay. When
alarm and load trimming scheme is not used; overcurrent PSM will be
corresponding to its LV side full load current. In case of adoption of alarm
and load trimming scheme; overcurrent PSM would be 105-110%. Earthfault PSM
shall be corresponding to 20% of transformer full load current as explained in
previous section.
LV side overcurrent and earthfault
relay time of operation shall be 350 ms for fault current considering fault on
LV bus. This will allow sufficient time for clearing the fault by LV feeder
breaker.
We
may select Highset setting corresponding to 70% of LV bus fault current with
time delay of 350 ms. This is due to two reasons.
1.) As we know that fault level at any
bus is calculated considering all elements of the power system and all
generators are in service. Actual fault level is always less than this
depending on outages on element and generators and fault impedance. If we
select HS current setting as 100% of LV bus fault level chances of it’s
operation will be very remote owing to above fact. Hence
we have to select HS current setting less than this calculated fault current
value to ensure its operation. It may be less by any quantity typically ranging
from 70% to 90%. To ensure maximum chances for operation of HS element we have
chosen 70%. Typical operating characteristics for LV side and HV side relays
plotted against common LV side fault current on X axis is as shown here.
2.) Figure also shows that with use of
HS by this way LV operating characteristics gets a shape where time discrimination between HV side relay and LV side relay
goes on increasing as fault current decreases (which is true for most of the
cases) from maximum possible fault current.
Very useful and illustrative ...
ReplyDelete