Problem
Consider a S/S having
two transformers of (a) 132/33kV 25 MVA having leakage reactance of 9.5% and
(b) 132/33kV 50 MVA having leakage reactance of 12.5%. Let the S/S source
impedance be negligible as compared to transformer leakage reactance. Find out
the 3-phase and 1-phase fault current for 33kV Bus fault.
Solution
Consider 50 MVA as base
MVA
Hence XT1-50MVA
= XT1-25MVA*(50/25) = 9.5*2 = 19% ----- ( using formula – 2)
XT2 = 12.5%
X = XT1||XT2
= 19*12.5/(19+12.5) = 7.54%
3-Ph short circuit MVA
= 50x100/7.54% = 663 MVA ---- (using formula – 3)
1-Ph short circuit MVA
= 3x50x100/(7.54+7.54+7.54) = 663 MVA (using formula – 4)
(As for transformer X1
= X2 = X0)
For 33kV voltage 1 MVA
= 17.5 Amp
Hence this current will
be 17.5*663 = 11602 Amp.
80% of this current
shall be 9281 Amp
Comments
Fault current for
faults at transformer LV bus increases with transformer capacity. If
transformer operates in parallel fault current will be still more.
Generally 100 MVA selected as base MVA. Here higer rating transformer selected as base MVA
ReplyDelete