Introduction
Electrical power get
transmitted to very long distance using Extra High Voltage. Voltage equal and
exceeding 66kV is called EHV. Thus in transmission system most faults causes
due to insulation failure. This insulation failure causes heavy current flow
through elements of power system for which the elements are not designed and
other adverse effects. Hence it becomes necessary to protect the power system
by disconnecting the faulty element using protection system and circuit
breaker.
To save the power system
during this fault it is necessary to design the protection system and circuit
breakers correctly. Also it is necessary to adopt the protection system
properly by settings its’ parameter correctly. And for this it is necessary to
have precise estimate of these fault currents and other system parameters
during fault.
Modelling of Power
System Elements
Every
part of power system under consideration for modeling consists of various
elements. Main elements of the power system are-
1) Synchronous
Generators
2) Transformers
3) Transmission
Lines
4) Part
of power system beyond current scope of modeling - Grid
For
engineering calculations such as load flow and fault calculations it is
necessary to model the above said power system elements with its equivalent
electrical circuit. While modeling the power system; transformer and
transmission line can be represented as an impedance (simplest form). Whereas
synchronous generator and grid can be represented by a voltage source in series
with an impedance. Here we will discuss how to model them for fault current
calculations
Synchronous Generators: -
Representation of synchronous generator changes depending upon time frame under
consideration after inception of fault. The overall series reactance for
synchronous generator is not constant but varies with time after inception of
fault. Synchronous generator can be represented by a voltage source in series
with an impedance equivalent to armature reaction and armature leakage
reactance. Just after fault it is Sub-transient reactance (
) from
0.1 sec to 3.0 sec after fault it is transient reactance (
) and
after that it is steady state reactance (
). For
deciding breaker current interruption rating sub-transient reactance needs to
be used while for transient stability study transient reactance to be used.
Here
subscript d stands for direct axis reactance. There are two reactance for
synchronous generator a) Direct axis b) Quadrature axis and for cylindrical
rotor type these both are equal, most of our synchronous generators are cylindrical
rotor type. Moreover even for salient pole type synchronous though the direct
and quadrature axis reactance are different; but as during fault current lags
voltage by nearly 900 hence effect of quadrature axis reactance is
negligible. Hence for fault current
calculations synchronous generators can be represented simply by
=
in
series with a constant voltage source.
Transmission Lines: - From
available data of conductor used for the transmission line and spacing it’s
impedance per kilometer length can be calculated. Also it is generally made
available by the Corporate Office. After multiplying this known impedance per
kilometer by length of the line we get the series impedance of the transmission
line. Generally resistance of transmission line is very less as compared to its
reactance and thus for fault calculations resistance is neglected and
transmission line is represented by equivalent reactance only.
Transformer: -For
transformer this impedance is equivalent to winding resistance in series with
transformer leakage reactance. For fault calculations resistance is neglected
and transformer is represented by equivalent leakage reactance only.
Grid: - The
part of power system which is beyond our current scope of modelling can be shown
as single impedance in series with single source (Thevnin’s equivalent
impedance in series with equivalent source). Where
(for
details see section – Formula for calculating 3-Ph fault current)
The
modeling can be best explained through an example. Next page Fig-1 shows a
representative power system whereas Fig-2 shows its’ equivalent circuit.
Here
in Fig-2 we have not shown any numerical values and during further discussion
the procedure for finding out these values will be explained.
PU Representation of power
system
In
power system multiple voltage level exists hence it is customary to represent
element impedances numerically using percentage values (Percent Value = PU
valuex100). Because once an element represented by its’ percentage value the
value remains same either referred from HV side or LV side of the transformer. Any
power system can be represented fully by four quantities viz. MVA and kV at
busses and current through elements and impedances of those elements. If the
power system is to be represented by pu quantities above mentioned quantities
are to be divided by respective base values. thus
These
quantities are so related that selection of any two quantities defines other
two quantities. Generally MVA and kV are selected as base quantities and base
current and base impedance get defined as
For
DC Circuit we know P = V*I = V*V/R = V2/R Thus R = V2/P
thus for AC circuit
OR
simple to remember
Excellent work. Your presentation is very simple & even layman can understand the things.
ReplyDelete