Solution
The
line conductor size, CT ratio and fault levels at bus-B are as shown in above
figure. Here for calculation purpose consider a fault on line but very near to
bus-B. In this case 50% fault current will be contributed by line under
consideration. Considering this fault current Relay setting calculations are
performed as previous.
Calculations
for O/C settings:
From table-1 thermal
rating of the line is 487 A. Hence
Optional Setting
High-Set for O/C equal
to 80% of fault contribution for O/C fault
= 0.8*2500/800 = 2.5
Amp with HS delay 350 ms
Calculations
for E/F settings:
a. For Overcurrent Relay MTA = +450 or 450
leading
b. For Earth Fault Relay MTA = -450 or 450
lagging
Optional Setting
High-Set for E/F equal
to 80% of fault contribution for earth fault
= 0.8*1500/800 = 1.5
Amp with HS delay 350 ms
Comments
In this case for remote
bus that means bus-A fault there will not be any contribution from bus-B; as
bus-B is not having any source. Hence fault current considered for calculations
of O/C and E/F setting at receiving end is the current contributed by the line
for the fault very near to bus-B. Obviously for double circuit radial line this
fault current will be half of receiving end bus total fault current.
In problem statement ..... Calculate the settings of Non-Directional O/C E/F relay provided at Bus-B. There shall be ..... Calculate the settings of Directional O/C E/F relay provided at Bus-B.
ReplyDeleteCorrecetd
ReplyDelete