Irrespective of transformer LV side
protection scheme selected; the methodology for deciding overcurrent and
earthfault relay settings remains same.
For Non-Directional (Reverse Direction i.e. towards LV bus) setting methodology
for PSM, TMS and HS is as below.
When alarm and load trimming scheme
is not used; overcurrent PSM will be corresponding to LV side full load current
of respective transformer. In case of adoption of alarm and load trimming
scheme; overcurrent PSM would be 105-110% of LV side full load current of
respective transformer. Earthfault PSM shall be corresponding to 20% of
transformer full load current as explained in previous section.
LV side overcurrent and earthfault
relay time of operation shall be 350 ms for 70% of fault current contribution
by respective transformer considering fault on LV bus. Here 70% of fault
current selected to shape the characteristics properly when we are using it
along with HS element. Also it allows for fault resistance and 33kV feeder
impedance; when fault is remote from LV bus. In case of non-availability of HS
element one may prefer to select this value as 100%.This will allow sufficient
time for clearing the fault by LV feeder breaker.
We may select Highset setting
corresponding to 70% of LV bus fault current contribution by respective
transformer. Time delay for HS shall be 350 ms.
For Forward Direction (Towards Transformer) setting methodology for PSM,
TMS and HS is as below.
Overcurrent PSM will be
corresponding to LV side full load current of respective transformer.
Earthfault PSM shall be corresponding to 20% of transformer full load current
as explained in previous section.
LV side forward direction
overcurrent and earthfault relay (or relay element) works as backup to
Differential Protection; time of operation shall be minimum. Hence TMS shall be
selected as 0.05.
We may select HighSet setting
corresponding to 70% of LV LA fault current contribution by respective
transformer. Time delay for HS shall be 50 ms.
You may have better understanding of
the methodology of deciding overcurrent and earthfault relay setting in case of
transformers after going through next two examples. First example demonstrates
setting methodology in case of transformers operating separately, while second
example explains setting methodology in case of transformer operating in
parallel.
Time delay for LV Forward HS to be selected 50mS. Selection of 70% of bus fault level nicely explained.
ReplyDelete