What
is bias? Why it is required? Why differential protection is called Bias
Differential Protection? Bias is applied to transformer differential protection
for the same reason as any unit protection scheme – to ensure stability for
external faults while allowing sensitive settings to pick up internal faults.
Ratio and phase angle correction are done to achieve stability for external and
through faults. But power transformers are equipped with on load tap changers
(OLTC) generally provided on HV windings. In general the voltage variation
achieved through tap changing is in the range of +5% to -10%. Ratio correction
of HV & LV CT secondary current is done at normal tap. This equilibrium
achieved at normal tap may not hold for other taps during external or through
faults reflected on transformer. Hence, the differential protection provided to
power transformer will remain stable at normal tap and may mal-operate at other
taps under through faults. By selecting minimum bias to be greater than sum of
the maximum tap of the transformer and possible CT errors, mal operation of the
protection can be avoided in case the transformer is being operated at other
taps. How bias setting helps to avoid mal-operation of the differential
protection is illustrated through following figures 4.0 (A to D).
Figure 4.0 B.External fault on transformer with Tap No.13.
Diff. Pick-up =15%(0.15A),Bias =30%(Assumed)
Modified Diff.Pick-up due to Restraining Effect of Bias
IdiffMod =0.30 x (10+11.1)/2+ 0.15 =3.165 +0.15 =3.315A.
Actual Diff.Current= 1.1A (IHV – ILV)
As the Actual Diff Current is less than the Modified Diff. current, protection will remain stable under this through fault.
No comments:
Post a Comment