The
zero sequence current will flow through the transformer in case of external
earth fault. This current will be seen as unbalance by differential protection
if the protected power transformer cannot transform this zero sequence current
to other side. This will happen in case of star connected transformers.
Transformers of this type do not transform zero sequence current. This current
will flow only in earthed star connected winding. In such cases, an external
earth fault on star side of the transformer causes the zero-sequence current to
flow on star side only and not on other side. This results in false
differential / unbalance current consisting exclusive of zero-sequence current.
This will lead to un-necessary tripping of power transformer for external earth
fault. Therefore, this current needs to be filtered out from fundamental
component of differential current to avoid un-necessary operation. In case of
static and electromechanical relays zero sequence current are filtered out by
using delta connected interposing CTs. For digital / numeric relays this is
achieved through relay software. The zero sequence current entering the
transformer having Delta connected winding will circulate in the delta winding
itself. Hence, for delta connected windings of the transformers, zero sequence
filtering is not required. Table No. – 1 summaries the phase compensation and
zero sequence filtering requirements of various transformers as per their
vector groups.
No comments:
Post a Comment