The
magnetizing inrush phenomenon is associated with a transformer winding which is
being energized where no balancing current is present in the other winding(s).
This current appears as a large operating signal for the differential
protection. Special measures are taken with the relay design to ensure that no
mal-operation occurs during inrush.
The
phenomenon of magnetizing inrush is a transient condition that occurs when a
transformer is energized. To minimize the cost, weight and size of the power
transformer, core of the transformer is designed to operate near to ‘knee
point’ of the magnetizing characteristic. Consequently, only a small increase
in core flux above normal operating level will result in high magnetizing
current. Under normal steady–state condition, the magnetizing current associated
with the operating flux level is relatively small. However, if a transformer
winding is charged at voltage zero, with no remnant flux, flux level during
first voltage cycle (2 x normal flux) will result in core saturation and high
non-sinusoidal magnetizing current waveform – as shown in Figure 3.0 .This
current is referred as magnetizing inrush current and will be seen by the only winding
which is charged and may persist for several cycles. Following factors affect
the magnitude and duration of magnetizing inrush current.
- Residual flux.
- Point on wave switching
- Number of banked transformers
- Transformer design and rating
- System fault level
The
magnetizing inrush phenomenon described above produces current input to the
energized winding which has no equivalent on other windings. The whole of the
inrush current therefore appears as unbalance and the differential protection
is unable to distinguish it from current due to internal fault. This will lead
to mal operation of the differential protection during the charging of the
transformer. Since, this phenomenon is transient; stability can be maintained
by providing small time delay in operation. However, this time delay also
delays operation of the relay in the event of internal faultoccurring at switch-on-to
fault, this method isnotused.
The
inrush current, although generally resembling normal in-zone fault current,
differs greatly when waveforms are compared. This difference in the waveforms
of normal fault and inrush current can be used to distinguish between
conditions. The inrush current contains all harmonics. Predominant is second
harmonic. Proportion of second harmonic varies somewhat with the degree of
saturation of core and exists always in inrush current. Normal fault current
does not contain second harmonic component. Hence, the differential protection
can be blocked if percentage of certain level of second harmonic current is
detected during the charging of transformer, thereby mal operation of the
protection can be avoided.
No comments:
Post a Comment