of HV and LV CTs of the transformer is done to approximately match the rated
primary and secondary currents. Hence, the current from the HV & LV side
CTs may not match correctly under load and through fault conditions. This
unbalance may lead to operation of differential protection. Therefore, for
correct operation, HV & LV replica currents entering the differential relay
should match. In case of digital / numeric relays this is done by providing
ratio correction factors for both HV & LV CTs. Depending upon the Digital
relay type, either the correction factor needs to be computed and entered
during settings or the relay may calculate the same on furnishing the required
details. This was done by providing Interposing CTs incase of electromechanical
relays.