Overcurrent
current protection is obviously implements as the first protection in
electrical system. At its basic level it was just a fuse wire protection. With
the advancement in technology and electrical system requirements; over current
relays and breakers has evolved as protection system. We will discuss the
philosophy behind adopting over current protection with the help of an example.
Logic-1: Discrimination by Current
Case-A: No appreciable change
in impedance.
Theoretically
relay R1 expected to protect Line-A-B against fault at Bus-B. Relay R2 expected
to protect Line-B-C against fault at Bus-C and relay R3 expected to protect the
transformer against fault at Bus-D. Now let we have set the relay at R1 to
operate whenever current exceeds 3715 Amp and likewise other relays too. However,
there are two important practical points that affect this method of co-ordination
a.
it is not practical to distinguish between a fault at X and a fault at Y, since
the distance between these points may be only a few metres, corresponding to a
change in fault current of approximately 0.1%
b.
in practice, there would be variations in the source fault level, typically
from 5250 Amp to 2550 Amp. At this lower fault level the fault current
would not exceed 3715 A, even for a line fault close to B (say at point X). A relay set at 3715 A would not protect any
part of the line section concerned.
Discrimination
by current is therefore not a practical proposition for correct grading of R1 and
R2.
Logic-2: Discrimination
by Time of Operation
As
explained in previous section it is not possible to discriminate between fault at
X and Y by current measurement. The alternative to this is discrimination by
time of operation. Hence to protect the Line-A-B by relay R1 and Line-B-C by
relay R2 we will adopt its operational current setting equal but operational
time setting different (t1 and t2 respectively). Let operational current for
relay R1 and R2 is kept same and considering safety margin 1.5 times for fault
at Bus-C it would be 3385/1.5 = 2256 A with t1 > t2 it will discriminate the
operation of relay R1 for fault on Line-A-B and operation of relay R2 for fault
on Line-B-C.
The
practical problem with such type of discrimination are
a) Irrespective
of fault current; time of relay operation is same. Actually high current faults
are sever and needs to be cleared early.
b) Relay
near the source has higher time of operation. Actually whenever the relay is
near the source, the element protected by the relay exposed to more fault
current hence needs to be cleared early.
No comments:
Post a Comment