Over flux / Under frequency protection:


                  Over fluxing or over excitation of a transformer connected to the terminals of a generator, can occur if the ratio of voltage to frequency exceeds certain limits. High voltage or low frequency, causing a rise in the V/Hz ratio, will produce high flux densities in the magnetic core of the transformer. This could cause the core of the transformer to saturate and stray flux to be induced in un-laminated components that have not been designed to carry flux. The resulting eddy currents in solid components (core bolts and clamps) and end of core laminations can cause rapid overheating and damage.

Transformer over fluxing might arise for the following reasons:
High system voltage
Generator full load rejection
Ferranti effect with light loading transmission lines
Low system frequency
Generator excitation at low speed with AVR in service Geo-magnetic disturbance
Low frequency earth current circulation through a transmission system

                 The initial effects of over fluxing will be to increase the magnetizing current of a transformer. This current will be seen as a differential current. If it reaches a high level there would be a risk of differential protection tripping. Persistent over fluxing may result in thermal damage or degradation of a transformer as a result of heating caused by eddy currents that may be induced in non-laminated metalwork of a transformer. The flux levels in such regions would normally be low, but excessive flux may be passed during over fluxed operation of a transformer.

              The following protection strategy is proposed to address potential over-fluxing conditions:


Maintain protection stability during transient over-fluxing           
Ensure tripping for persistent over-fluxing

                    By measuring the 5th Harmonic component in the differential current, the over-fluxing can be identified. The ratio of fifth to fundamental component ic compared with set value. If exceeds the set value, the transformer can be isolated. Further, where there is any risk of persistent geomagnetic over-fluxing, with normal system voltage and frequency, the 5th harmonic differential current facility could be used to initiate tripping after a long time delay. To ensure tripping for persistent over-fluxing, due to high system voltage or low system frequency, time delayed Volts per Hertz protection is provided. Protection against damage due to prolonged over-fluxing is offered by a V/f protection element with a variable time tripping characteristic. The setting flexibility of this element, by adjustment of the time delay at various V/f values, makes it suitable for various applications. The manufacturer of the transformer or generator should be able to supply information about the short-time over-excitation capabilities, which can be used to determine appropriate settings for the V/f tripping element. The variable time over-fluxing protection would be used to trip the transformer directly.


No comments:

Post a Comment