MTA
for Line-Ground Fault
Consider R-Ph to ground
fault. During this fault R-Ph voltage will decrease and R-Ph current will be
lagging to R-Ph voltage nearly by 900 as shown in the figure-1.
However
Earth fault relay current In will be 1800 out of phase
with respect to R-Ph current as shown in figure-2
Thus depending up on fault impedance
R-Phase current may be anywhere as shown by red shaded area and thus
corresponding earth fault relay current may be anywhere as shown by green
shaded area for figure-3.
As
there may be the fault on any phase and as during fault; volatge of faulty
phase reduces nearly to zero it is not desirable to consider volatge of faulty
phase for deciding the direction of fault current. It is obvious choice to use
residual voltage V0 (vector sum of Vr, Vy and Vb) for deciding the
direction of fault current as shown in the figure.
To include all this probable area for
earth fault current it is necessary to redefine zone of forward direction with
respect to polarizing voltage V0. Thus line AB is selected as new
dividing line for operating direction (Forward) and Non-Operating direction
(Reverse). Perpendicular line to this dividing line is line C-D. Now we can see
that line CD lags V0. For electromagnetic relays this angle use to
be -450. Now for numerical relay this angle is settable still
recommended value is -450.
No comments:
Post a Comment