the power system under consideration 315 MVA ICT and 200 MVA ICT needs to be
replaced by respective three terminal network. As there is no source connected
to ICT tertiary it need not be connected to +Ve reference bus and –Ve reference
bus in respective network but as tertiary is Delta connected it needs to be
connected to zero reference bus. Accordingly calculations and sequence networks
for the power system would be as below.
1) Generator
Xg1(new)
= Xg1(given)*(Base MVA/Rated MVA)
Xg1(new) = 0.15*100/60 = 0.25 or 25%
-Ve and Zero Sequence reactance for
generator are same as +Ve sequence reactance
2) Generator
transformer
Calculate
values for XP, XS and XT for 100 MVA ICT from
name plate values of Xps, Xpt and Xst are Xps = 14%, Xpt = 40%, Xst = 28% thus
XP
= (Xps + Xpt – Xst) = 13%
XS
= (Xps + Xst – Xpt) = 1%
XT
= (Xpt + Xst – Xps) = 27%
For
Transformers and ICT -Ve and Zero Sequence reactance are same as +Ve sequence
reactance
3) 132kV
Transmission lines
Ohmic value of line reactance
= 0.4 * 35 = 14 Ω
Positive Sequence Pu value XL11
= XL21 = 14*100/(132)2 = 0.0803 or 8.03%
For line zero sequence
reactance will be 3 times more (or as equal to actual value available), thus
XL10 = XL20
= 24.09%
4) Similarly
for 220kV Lines
XLa1
= XLb1 = 4.54% and XLa0 = XLb0 = 13.62%
5) For
200 MVA and 100 MVA ICTs
For
200 MVA ICT from name plate values of Xps, Xpt and Xst are Xps = 13%, Xpt = 37%,
Xst = 26% thus
XP1
= (Xps + Xpt – Xst) = 12%
XS1
= (Xps + Xst – Xpt) = 1%
XT1
= (Xpt + Xst – Xps) = 25%
For
the base of 100 MVA these values will be
XP1
= 6.0%
XS1
= 0.5% and
XT1
= 12.5%.
For
Transformers and ICT -Ve and Zero Sequence reactance are same as +Ve sequence
reactance.
For
100 MVA ICT tertiary delta is open hence
XT21
= 0.127*100/100 = 0.127 (or 12.7%) again For Transformers and ICT -Ve and Zero
Sequence reactance are same as +Ve sequence reactance.
1) Power
Grid
Using formula
Xs1% = 100x100/1200
= 8.33%
Now to find out Xs0 use formula
Thus
2*8.33
+ Xs0% = 3*100*100 / 1000
2*8.33
+ Xs0% = 30
Hence
Xs0% = 30 – 16.66%
Xs0
= 13.34%
From
these values we can draw the +Ve, -Ve and Zero sequence network and considering
SLG fault at 132kV Bus we can interconnect them as shown below.
Reducing +Ve or –Ve
sequence network to single reactance between respective reference bus and fault
point is straight forward. However to reduce zero sequence network to a single
reactance requires conversion of star to delta in respect of 220/132kV 200 MVA
ICT equivalent circuit.