From
above discussion we can also note that zero sequence current can flow only if
there is return path. Hence for Y-y connected transformer without neutral
earthed (either of HV side or LV side) there will not be zero sequence current
through transformer. Similarly for
D-y
connections with LV side neutral earthed zero sequence current will flow
through delta side only and will not reflect into power system connected to HV
side of the transformer. This fact can be represented as shown in figure. In
this case zero sequence impedance of transformer is same as that of its’ +Ve
sequence; only connections in zero sequence network differs depending upon
transformer winding connection type. While representing zero sequence network
of the power system; if transformer HV
or LV side winding is Y connected and earthed that side of the transformer get
connected to power system. Whereas Delta connected transformer winding get
connected to zero sequence reference bus. Zero sequence equivalent circuits
for different types of transformer are shown in the figure. Fortunately in
transmission system most of the transformers are Y-y connected with both side
neutral grounded. In such case zero sequence network of the power system is
same as positive sequence network (except change in zero sequence impedance
values for transmission lines).
No comments:
Post a Comment