Problem
Consider a radial 132kV
line emanating from 132kV Bus-A; and terminating on 132kV Bus-B. Calculate the
settings of Non-Directional O/C E/F relay provided at Bus-B.
Solution
The line conductor
size, CT ratio and fault levels at remote bus (i.e.bus-B) are as shown in above
figure and same as example-1. Hence we can adopt same settings as that of relay
in example-1. However being non source bus there will not be any fault feeding
from Bus-B. Hence to serve this relay as protection to 132kV Bus-B faults; we
have to keep it non directional as shown in above figure. Also to protect
downstream network of transformer LV side we will adopt its operational time of
350 ms instead of 500 ms.
Calculations
for O/C settings:
From table-1 thermal
rating of the line is 487 A. Hence
Optional Setting
High-Set for O/C equal
to 80% of fault contribution for O/C fault
= 0.8*5000/800 = 5.0
Amp with HS delay 350 ms
Calculations
for E/F settings:
High-Set for E/F equal
to 80% of fault contribution for earth fault
= 0.8*3500/800 = 3.5
Amp with HS delay 350 ms
Comments
Often it
is necessary to validate the PSM and TMS settings of overcurrent and earth
fault relay of radial line so as to have sufficient time discrimination with
transformer HV side relay for fault on transformer HV side as well as LV side. This
is explained by Example-5
No comments:
Post a Comment