Consider
a radial double circuit 132kV line emanating from 132kV Bus-A; and terminating
on 132kV Bus-B. Calculate the settings of Directional O/C E/F relay provided at
Bus-A.
Solution
The
line conductor size, CT ratio and fault levels at remote bus (i.e.bus-B) are as
shown in above figure. Here fault current contributed by each line will be half
of the total fault current.
Calculations
for O/C settings:
From table-1 thermal
rating of the line is 487 A. Henc.
Optional Setting
High-Set for O/C equal
to 80% of fault contribution for O/C fault
= 0.8*2500/800 = 2.5
Amp with HS delay 500 ms
Calculations
for E/F settings:
Optional Setting
High-Set for E/F equal
to 80% of fault contribution for earth fault
= 0.8*1750/800 = 1.75
Amp with HS delay 350 ms
Set
a. For Overcurrent Relay MTA = +450 or 450
leading
b. For Earth Fault Relay MTA = -450 or 450
lagging
Comments
For
double circuit line; fault current get divided into two circuits. Hence for
same fault levels of receiving end and same CT ratio at source end obviously
TMS for double circuit line will be less with respect to that of single circuit
line. Compare settings results of this example with that of example-1