Problem
Consider a radial 132kV
line emanating from 132kV Bus-A; and terminating on 132kV Bus-B. Calculate the
settings of Directional O/C E/F relay provided at Bus-A.
Solution
The line conductor
size, CT ratio and fault levels at remote bus (i.e.bus-B) are as shown in above
figure. Usually this O/C E/F backup relay is directional even though the line
is not operating in the grid.
Calculations
for O/C settings:
From table-1 thermal
rating of the line is 437 A. Hence
Optional Setting
High-Set for O/C equal
to 80% of fault contribution for O/C fault
= 0.8*5000/800 = 5.0
Amp with HS delay 500 ms
Calculations
for E/F settings:
(Or decide by
referencing IDMT characteristics curve – read comments)
Optional Setting
High-Set for E/F equal
to 80% of fault contribution for earth fault
= 0.8*3500/800 = 3.5
Amp with HS delay 500 ms
Comments
As
now a days there is wide spread availability of calculating devices hence
referencing IDMT curve for deciding time of operation of O/C E/F relay from
multiple of current is became obsolete. However you have to understand and
remember the respective formulae carefully.