Corporate
office carries out fault level calculation studies for entire power system for
entire power system and provides 3-Ph and 1-Ph fault MVA values for every bus
in the grid. Thus using reverse engineering and formula for 3-Ph fault level
mentioned above one can write as
Then
we can also write as
Knowing
the value of X1s and as we know that X2s = X1s
above equation reduces to
After
putting value of X1s and 1-phase short circuit MVA at that bus in
above equation we can find out X0s
The
method for calculation of 1-Ph fault level can be best understood after going
through solved example. For example purpose we will consider same power system
as discussed for 3-Ph fault calculations.