For protection of EHV lines generally
directional overcurrent and earth fault relays are used. In case of directional
relay it is necessary to set correct MTA for over current as well as earth
fault relay. Maximum Torque Angle depends upon factors such as source impedance
and method adopted for earthing of generators and transformers. In transmission
system generally solidly earthed transformers are used. Hence it is common to
use following settings for MTA
a. For Overcurrent Relay MTA = +450 or 450
leading
b. For Earth Fault Relay MTA = -450 or 450
lagging