To
avoid this overlap of Method-A let we have to set HV side relay R3 time as 500 ms for fault
on LV side of transformer. With safe time grading margin of 200 ms we adopt relay
operation time of 700 ms for R2 and 900 ms for R1.
Related calculations are tabulated below.
R3
|
R2
|
R1
|
|
Relay
operating current setting
|
240
|
400
|
600
|
Fault
Current Considered for Calculation of ROT
|
1377
|
1377
|
1377
|
Remarks
for considered fault current
|
Current reflected on transformer HV side
for transformer LV side fault
|
Current reflected on transformer HV side
for transformer LV side fault
|
Current reflected on transformer HV side
for transformer LV side fault
|
Fault
current as multiple of set value
|
5.74
|
3.44
|
2.29
|
Relay
Operational Time with TMS = 1
|
3.94
|
5.59
|
8.36
|
ROT
Required
|
0.50
|
0.70
|
0.90
|
Remarks
for considered ROT
|
Transformer LV side
relay operational time + Time Gradation 0.2 sec
|
Relay R3 operational
time for fault current + Time Gradation 0.2 sec
|
Relay R2 operational
time + Time gradation 0.2 sec
|
TMS
|
0.127
|
0.125
|
0.108
|
Validation
of adopted settings