At a 220/132kV Sub-Station there are two ICTs operating in parallel. ICT-I having capacity of 200 MVA. Whereas the capacity of ICT-II is 100 MVA.
ICT-I HV Side CT Ratio is /1 Amp. while it's IV Side CT Ratio is /1 Amp.
ICT-2 HV Side CT Ratio is /1 Amp. while it's IV Side CT Ratio is /1 Amp.
HV and IV Bus fault levels and contribution of fault current by each ICT for HV and IV bus fault is as shown in the following table
Calculate HV side and IV side **FOR ICT-I** backup relay setting for IDMT and HS element.
Bus Fault Levels MVA | ||
Bus | Fault Type | Fault Level in MVA |
ICT HV Bus | 3-Phase (LLL) | |
1-Phase (SLG) | ||
ICT IV Bus | 3-Phase (LLL) | |
1-Phase (SLG) |
Fault Current contribution by ICTs | ||||
Fault At | Type | ICT | Winding | Ampere |
ICT HV Bus Fault | 3-Phase (LLL) | ICT-I | HV Winding | |
IV Winding | ||||
ICT-II | HV Winding | |||
IV Winding | ||||
1-Phase (SLG) | ICT-I | HV Winding | ||
IV Winding | ||||
ICT-II | HV Winding | |||
IV Winding | ||||
ICT IV Bus Fault | 3-Phase (LLL) | ICT-I | HV Winding | |
IV Winding | ||||
ICT-II | HV Winding | |||
IV Winding | ||||
1-Phase (SLG) | ICT-I | HV Winding | ||
IV Winding | ||||
ICT-II | HV Winding | |||
IV Winding |
1.b) HV E/F PSM = %
2.b) IV E/F PSM = %
3.b) HV O/C Relay Current for above fault = Amp.
3.c) HV O/C Relay Current Multiple = xIset
4.b) TMS to have Time of operation 500ms =
5.b) HV E/F Relay Current for above fault = Amp.
5.c) HV E/F Relay Current Multiple = xIset
6.b) TMS to have Time of operation 500ms
7.b) ICT-1 HV CT Current for HV LA LLL Fault = Amp.
7.c) ICT-1 HV CTR = /1 Amp.
8.b) O/C HV Relay Current for calculations of HS2 = Amp.
9.b) E/F HV Relay Current for calculations of HS2 = Amp.
14.b) IV O/C Relay Current for above fault = Amp.
14.c) IV O/C Relay Current Multiple = xIset
15.b) TMS to have Time of operation 500ms =
16.b) IV E/F Relay Current for above fault = Amp.
16.c) IV E/F Relay Current Multiple = xIset
17.b) TMS to have Time of operation 500ms
18.b) ICT-1 IV CT Current for IV LA LLL Fault = Amp.
18.c) ICT-1 IV CTR = /1 Amp.
19.b) O/C HV Relay Current for calculations of HS2 = Amp.
20.b) E/F HV Relay Current for calculations of HS2 = Amp.