In case of non-availability of HV
bus fault levels or other resources required for detail calculations; one may
choose for quick calculations. Here for calculations of relay time of operation
with TMS = 1; either scientific calculator or document for Standard Inverse
characteristic curve plotted on double log graph will require.
In such case LV bus fault current
shall be considered as 70% of calculated fault current neglecting source
impedance. As +Ve sequence and zero sequence leakage reactance of the
transformer is same calculated 3-Ph short circuit current and 1-Ph short
circuit current for LV bus will be same. In other words it is just sufficient
to calculate 3-Ph short circuit current for LV bus and to consider same for
1-Ph short circuit current.
If transformer operates in parallel
and when there is a through fault (fault on LV Bus); current shared by them
will be in proportion to its capacity. Also while transformer operates
separately it’s through fault current is proportional to capacity.
Thus when source impedance is
neglected; it is not needed to adopt different procedures for calculations of
short circuit MVA for transformer through fault; when transformers operating
separately or operating in parallel. We can directly calculate T/F short
circuit MVA using same formula for both cases.
For 33kV Bus
Also O/C PSM shall be decided
considering LV full load current as per name plate details and HV full load
current equal to HV current on normal tap.
To understand the methodology;
readers are requested to go through the solved example. Though the example
solved using Excel sheet it is encouraged to solve it by hand calculations.
Limitations of Approximate Calculations: Though the decision of approximate
calculations may lead to unselective tripping of the transformer if actual
fault current is very much higher than considered fault current (70%). In such
case by observing the DR one may revise his decision. However for remote
sub-station fault current may be even less than considered for quick
calculation. Under such circumstances transformer may get subjected to risk.
Hence such decision shall be taken cautiously.
Actually for 132/33 kV 2X25 MVA
transformer with 132kV Bus as strong source; approximation considering 70% of
fault level neglecting source impedance may work. But for other cases following
table will help.
No comments:
Post a Comment