While using the definite time delay
protection in case of overcurrent and earthfault relay you should always be
cautious. Following things should be avoided.
1) Setting High Set element current of
HV side relay corresponding to LV bus fault reflected on HV with instantaneous
operation (Time Delay = 0 ms)
2) Setting LV side forward direction
High Set instantaneous (Time Delay = 0 ms). This setting may cause the relay to
mal-operate in case of very near LV bus fault due to transients. It is better
practice to set time delay for this element as 50 ms.
3) Setting LV side reverse direction
High Set current setting very less along with instantaneous operation. This
will definitely cause operation of transformer LV breaker along with feeder
breaker leading to unselective tripping.
4) As mentioned in section “Settings ….
When T/F operating separately” that as LV Bus fault current decreases time
discrimination between HV and LV relay increases. Converse of this is also
true. This happens more predominantly in case of use of HS for LV relay. Hence
if fault level increase it is necessary to review TMS settings.
Thus it is general tendency to keep
High Set current value to some unrealistic high value and thereby keeping this
feature in bypass state. In spite of all such odds it is recommended to use
High Set element cleverly as it may provide valuable information during
transformer tripping on fault and may assists in analysing the fault more
correctly and decision making accordingly.
Here we have shown 2 methods of
using High Set Element. Method 1 will work correctly. However method 2 will not
work. Because in 2nd method relay R3 to which IDMT characteristics
assigned will operate before to HighSet element and we will not get expected
operating characteristics. The figures shown are self-explanatory.
Fig-1
|
Fig-2
|
Correct Use of Highset
|
Incorrect Use of Highset
|
No comments:
Post a Comment