With
this discussion now let us model the power system shown in figure by using pu
values.
To start with let the base selected as 100 MVA for modeling the power system. You can select any value but it is normal practice to select 100 MVA as base MVA. Select base kV as 11kV for generator. This will fix the base kV of other elements of power system to its rated kV considering transformer voltage ratios in the power system. Thus base kV for 132kV line would be 132kV and for 220kV line it would be 220kV. Now we will decide abbreviation for pu reactance (neglect resistance for fault calculations) for different elements as below
To start with let the base selected as 100 MVA for modeling the power system. You can select any value but it is normal practice to select 100 MVA as base MVA. Select base kV as 11kV for generator. This will fix the base kV of other elements of power system to its rated kV considering transformer voltage ratios in the power system. Thus base kV for 132kV line would be 132kV and for 220kV line it would be 220kV. Now we will decide abbreviation for pu reactance (neglect resistance for fault calculations) for different elements as below
- 1) Generator Xg
- 2) Generator Transformer Xgt
- 3) 132kV Lines XL1, XL2
- 4) 220kV Lines XLa, XLb
- 5) 220/132kV ICTs XT1, XT2
Using
different formulae now we will calculate pu values of respective elements for
base MVA as 100 and base kV as rated kV of the element. Thus
1) Generator
and Generator transformer
Xg(new)
= Xg(given)*(Base MVA/Rated MVA)
Xg(new) = 0.15*100/60 = 0.25 or 25%
Xgt(new) = 0.15*100/100 = 0.15 or
15%
2) 132kV
Transmission lines
Ohmic value of line reactance
= 0.4 * 35 = 14 Ω
Pu value XL1 = XL2 =
14*100/(132)2 = 0.0803 or 8.03%
3) 220/132kV
ICTs
XT1 = 0.14*100/200 = 0.07 (or 7%)
XT2 = 0.127*100/100 = 0.127
(or 12.7%)
4) 220kV
Transmission lines
Ohmic value of line reactance
= 0.4 * 55 = 22 Ω
Pu value XLa = XLb =
22*100/(220)2 = 0.0454 or 4.54 %
5) Power
Grid
Using formula
Xth% = 100x100/1200
= 8.33%
Thus
now system model with percent values will be
The
impedance equivalent to grid is generally referred as source impedance
If SLD is shown, things gets explained better...
ReplyDeleteExcellent work.
Thanks for suggesting correction. SLD added, actually it is the same power system considered for discussion in section "Modelling of Power System Elements". The Same power system also used while discussing Unsymmetrical Faults. I will add this SLD to respective section too.
ReplyDelete